Samsung AM300MXVGNR4ET - Pipe Sizing Tables

Samsung AM300MXVGNR4ET
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
ENGLISH
H/P
ߥߥ࢏ߨǮ ߦߢ࢏ߢǮ
(D)
(E)(C)
(A)
(B)
(3)(2)(1)
ߨߣ࢏ߨǮ
kу࢏࣒ߣߥߧ࢏ߤǮ
Capacity (kW) Ęͱ࢏
Pipe size (mm)
Liquid pipe Gas pipe
ߥߥ࢏ߨǮ (1) Ø 12.70 Ø 28.58
ߩߥ࢏ߨǮ (2) Ø 19.05 Ø 34.92
ߣߥߧ࢏ߤǮ (3) Ø 19.05 Ø 41.28
Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table.
Outdoor unit capacity (kW)
(Cooling)
*Maximum pipe length within 90m *Maximum pipe length over 90m
Liquid pipe (mm) gas pipe (mm) Liquid pipe (mm) gas pipe (mm)
22.4 kW
Ø 9.52
Ø 19.05
Ø 12.70
Ø 22.22
ߤߤ࢏ߧǮߤߪ࢏ߣǮ Ø 22.22 Ø 25.40
note1)
ߤߪ࢏ߤǮߥߥ࢏ߨǮ
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
ߥߥ࢏ߩǮߦߢ࢏ߢǮ
ߦߢ࢏ߣǮߦߧ࢏ߢǮ
Ø 31.75
note2)
ߦߧ࢏ߣǮߧߢ࢏ߦǮ
Ø 15.88 Ø 19.05
ߧߢ࢏ߧǮߧߨ࢏ߢǮ
ߧߨ࢏ߣǮߨߥ࢏ߥǮ
ߨߥ࢏ߦǮߩߢ࢏ߥǮ
Ø 34.92 Ø 38.10
note3)
ߩߢ࢏ߦǮ߫ߪ࢏ߦǮ
Ø 19.05 Ø 22.22߫ߪ࢏ߧǮߣߥߧ࢏ߤǮ
Ø 41.28
Ø 41.28
ߣߥߧ࢏ߥǮߣߨ߫࢏ߢǮ
Ø 53.98
ߣߨ߫ߣǮߤߧߤߢǮ Ø 22.22 Ø 53.98 Ø 25.40
note1)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe
installed on the site, a socket is provided by default together with the outdoor unit.