Setting the MCU and Pipe Addresses (for HR Only)
Before running the Auto pipe pairing operation, be sure to close the front cabinet. If this operation
is run with the front cabinet open, the product may be damaged and the pipe addresses cannot be
correctly recognized.
To run the Auto pipe pairing operation, take the following steps:
1. Press the K2 button 13 times on the main PBA of the outdoor unit to start the Auto pipe pairing operation.
(Display : .)
ĮЇϩʒͱͱθϩʪΧʪθɇϩЇθʪߤߦ
ߤߦঙĮЇϩʒͱͱθϩʪΧʪθɇϩЇθʪߥߢঙ
ߥߢঙĮЇϩʒͱͱθϩʪΧʪθɇϩЇθʪ
Indoor temperature
ߤߦ
Main heating operation Main heating operation Main cooling operation
Indoor temperature
ߤߦ
Main heating operation Main cooling operation Main cooling operation
Each step is indicated on the outdoor unit display. (The whole operation takes about 25 to 55minutes
normally, depending on the number of indoor units connected. However, it can be operated for up to 2
hours to protect the compressor.)