Method to calculate total amount of additional refrigerant
ৄ Amount of additional refrigerant depending on the pipe length (
)
ৄ Amount of additional refrigerant for each indoor unit (
࣒࣑ͱЇϩͱ˙ɇʒʒϩͱɇθʪ˙θ˝ʪθɇϩ˙ͱθʪɇʀ˵
ʀͱʪʀϩʪʒʒͱͱθЇϩ࣒࢜ŵʪ˙ʪθϩͱϩ˵ʪϩɇɵʪ
ৄ Total amount of additional refrigerant =
+
࢜
Sum of total amount of additional refrigerant and the basic amount of refrigerant should not exceed
100kg. If the refrigerant exceeds 100kg, separate the module so that weight of the refrigerant doesn't
exceed 100kg.
kу࣒ͱθđߤߢߢǹǤࡥɵɇϑʀɇͱЇϩͱ˙θʪ˙θ˝ʪθɇϩϑߪߦ˝ࡥϩ˵ʪθʪ˙ͱθʪϩͱϩɇɇͱЇϩͱ˙ɇʒʒϩͱɇ
refrigerant (
+ ࣒ϑ˵ͱЇʒͱϩʪуʀʪʪʒ߫ߣߨ˝
Example of refrigerant calculation for HP models
Aɇϑϑѣʀɇϩͱ Size of liquid pipe
Length (m)
Unit amount
of refrigerant
(kg/m)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
×
࣑ × )
Liquid pipe (
)
Ø 6.35 35 0.02 0.7
5.575
Ø 9.52 50 0.06 3.0
Ø 12.70 15 0.125 1.875
Aɇϑϑѣʀɇϩͱ
Model name of
indoor unit
Number of units
Unit amount of
refrigerant (kg/EA)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
×
࣑ × )
Indoor unit (
)
4way cassette
࣑đߢߩߣĘߦUk²࣒
4 0.45 1.80
3.10
Slim duct
࣑đߢߧߨĘøUk²࣒
20.350.70
Slim duct
࣑đߢߦߧĘøUk²࣒
1 0.35 0.35
1way cassette
࣑đߢߥߨĘߣUk²࣒
10.250.25
ৄ Total amount of refrigerant ( + ) = 5.575+3.10 = 8.675 (kg)
Refrigerant pipe installation