Control Systems
18
II
Individual control systems
3. Wired remote controller
4) Option function
MWR-WE10N
Main
menu
4VC
menu
Function
SEG
Used
Default 3BOHF Unit
1
1
Wired remote
controller Option
TFUUJOHDIFDLJOH
(1)
$PPMJOH)FBUJOHTFMFDUJPO
10
$PPMJOH)FBUJOH$PPMJOHPOMZ
-
Use of wireless remote controller 2 1 0-No use, 1-Use -
."*/46#XJSFESFNPUFDPOUSPMMFS
3 0 0-MAIN, 1-SUB -
5FNQFSBUVSFVOJU 40
o$FMTJVT¡$o'BISFOIFJU¡'
2
Wired remote
controller Option
TFUUJOHDIFDLJOH
(2)
5FNQFSBUVSFTFOTPSTFMFDUJPO 10
0–Indoor unit, 1–Wired remote controller
-
Use of average temperature 2 0 0-No use, 1-Use -
Use of Auto mode 3 1 0-No use, 1-Use -
5FNQFSBUVSFEJTQMBZ 40
0–Set temperature,1-Room temperature
-
"$0O0GGCVUUPOGVODUJPO 50
o*OEPPSVOJU&37o *OEPPS
VOJUPOMZo&37POMZ
-
3
#MBEFTFUUJOH
checking
-PDLCMBEF 10 6OMPDL-PDL -
-PDLCMBEF 20 6OMPDL-PDL -
-PDLCMBEF 30 6OMPDL-PDL -
-PDLCMBEF 40 6OMPDL-PDL -
4
&37PQUJPO
4FUUJOHDIFDLJOH
Use of By-pass mode 1 0 0-No use, 1-Use
Use of Auto mode 2 0 0-No use, 1-Use
Use of air purification mode 3 0 0-No use, 1-Use
Use of external control 4 0 0-No use, 1-Use
5
Room temperature
compensation
Current room temperature
1, 2, 3 - _¡$
¡$
5FNQFSBUVSFDPNQFOTBUJPOWBMVF
4,5,6 - _¡$
¡$
6
number of connected
indoor units
Number of indoor units 1,2 0 0~16 -
/VNCFSPG&37T 3,4 0 0~16 -
7
5FNQFSBUVSFJODSFNFOUEFDSFNFOUVOJU¡$POMZ 1- ¡$¡$¡$ -
0
Factory option setting 1 -
0-Unchanged,
1-Factory setting
-
2
1
Software code 1~6 - Software code -
2
Software version 1~6 - Software version -
3
1
Indoor unit room temperature 1,2,3 - Room temperature ¡$
2
*OEPPSVOJU&7"*/UFNQFSBUVSF 1,2,3 - &7"*/UFNQFSBUVSF ¡$
3
*OEPPSVOJU&7"065UFNQFSBUVSF 1,2,3 - &7"065UFNQFSBUVSF ¡$
4
*OEPPSVOJU&&7TUFQ 1,2,3 - &&7TUFQ -
5
Indoor unit option
checking(1)
Use of central control 1 - 0-No use, 1-Use -
Use of drain pump 2 - 0-No use, 1-Use -
Use of electric heater 3 - 0-No use, 1-Use -
Use of hot water coil 4 - 0-No use, 1-Use -
6
Indoor unit option
checking(2)
Use of external control 1 - 0-No use, 1-Use -
Use RPM compensation 2 - 0-No use, 1-Use -
Filter time 3 - 0-2000 hours, 1-1000 hours -
Heating temperature compensation
4- ¡$¡$ -
&&7TUPQTUFQJOIFBUJOH 5- TUFQTUFQ -
4
1
Indoor unit option
setting
2)
*
Indoor unit main address 1, 2 -
Main address(00H~4FH,
Hexadecimal digits)
-
Indoor unit setup address
(Manual setting main address)
3, 4 -
Main address (00H~4FH,
Hexadecimal digits)
-
Indoor unit RMC address 5, 6 -
RMC address (00H~FEH,
Hexadecimal digits)
-
2
Indoor unit Product option code 1)* -
Indoor unit option code
-
3
*OEPPSVOJU*/45"--PQUJPO 1)* - Refer to the indoor unit
installation manual for details
-
4
*OEPPSVOJU*/45"--PQUJPO 1)* - -
Service mode