EasyManua.ls Logo

Samsung MCM-A300N - 2 DMS B-Net(Bacnet GW); Description of Parts

Samsung MCM-A300N
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
63
C
ENTRALIZED
C
ONTROL
S
YSTEMS
3) Description of parts
No.
Name
Description
LCD On/Off button and
Indoor unit operation indicator
Button : Turn on/off the LCD screen
Indicator
- Blue : Turns on if any one of the indoor unit is in operation.
- Red : Turns on if nay one of the indoor unit has an error
SD card slot
Use to back-up data on SD card or updating S/W
Power terminal $POOFDU"$_7)[QPXFS
Reset button
Use to reset Touch centralized controller
DI-1 terminal Terminal block for connecting digital input signal from 3rd party device.
DI-2 terminal Terminal block for connecting digital input signal from 3rd party device.
DO Terminal
Terminal block for digital output signal.
- Short : When any one of indoor units turns On
- Open :When all indoor units are off
485 communication terminal
8IFODPOOFDUJOHUPTFUMBZFS$POOFDUUPPVUEPPSVOJUPSJOEPPSVOJU''

8IFODPOOFDUJOHUPDPOUSPMMBZFS$POOFDUUPPVUEPPSVOJU0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FE
controller or DMS2 (R1/R2)
Compatible product
7 Conventional communication outdoor unit requires interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
Outdoor unit AM7777X777777
Controller
OnOff controller (MCM-A202DN)
Touch centralized controller (MCM-A300N)
DMS2 (MIM-D00AN)
BACnet gateway (MIM-B17N)
Lonworks gateway (MIM-B18N)