E-101
12
Select standard value.
X
Select detailed item value of selected factor or factor.
X
The item varies depending on the left factor when selecting detailed item value
from standard value.
Ex1) Factor : Current temperature of indoor unit 1,
Value of standard value : Enter 29
Ex2) Factor :
Remote controller usage of indoor unit 1,
Value of standard value : Select one among Enable RC, Disable RC and Cond. RC.
X
When selecting factor from standard value, it must be same with control item of
left factor.
Ex1) Factor : Power of indoor unit 1,
Factor of standard value : Power of indoor unit 2
Ex2) Factor : Current temperature of indoor unit 1,
Factor of standard value : Average current temperature of indoor unit 1 and 2
13
Select duration time usage.
X
Duration time means the time which the comparing conditions satisfy ‘True.
X
The duration time can be set from 1 to 60.
X
If you select duration time apply, the comparing condition will be 'True'.
To execute, maintain 'True' for duration time.
Note
XOnly 1 duration time can be set per control logic.
XThe tolerance range of duration time is maximum 1 minute. If you set the
duration time as 2 minutes, operation will be started between 2 and 3 minutes.