Installing and connecting the drain hose to the outdoor unit
In Heat mode, ice may accumulate. During defrost, check for condensate drain.
1. Insert the drain plug into the drain hole on the underside of the outdoor unit.
2. Connect a drain hose to the drain plug.
3. Ensure that condensation drain is working.
Frame
Ground
Estimated
snow fall
Snow-proof hood
Bottom surface of outdoor unit
Drain hose
Drain hole
Drain plug
Drain hole
Drain plug
t 5PTUPQESBJOQMVHGSPNDPOUBDUJOHUIFHSPVOEFOTVSFPVUEPPSVOJUJTSBJTFE
o ground.
t *OBSFBTXJUIIFBWZTOPXGBMMQJMFETOPXDPVMECMPDLUIFBJSJOUBLF
To avoid this incident, install a frame that is higher than estimated snow
fall. In addition, install a snow-proof hood to stop snow from piling on the
outdoor unit.
The outdoor unit is provided with sucient R-410A refrigerant. Do not vent R-410A into atmosphere: it is a uorinated
greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 2088.
You should evacuate the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it aects the compressor.
It may cause reduction of cooling capacity and malfunction. Use Vacuum Pump as seen in the picture.
t 8IFOJOTUBMMJOHNBLFTVSFUIFSFJTOPMFBLBHF8IFOSFDPWFSJOHUIFSFGSJHFSBOUHSPVOEUIFDPNQSFTTPSöSTU
before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor
operates with the service valve open, air can enter the system increasing pressure and may cause explosion and
injury.
Evacuating the connected pipes
English-49
INSTALLATION07