The parameter to set derivation time for PID control.
Setting ranges of ‘1.D’ are ‘OFF’,’1 ~ 6000 sec’.
Its initial setting is ’30 sec’.
The parameter to set apply for manual setting value in PID integral time
contents when Integral time(I) of PID control is ‘OFF’.
Setting value of ‘1.MR(Manual Reset) is not workable when setting value of ‘1.I’
is ‘OFF’.( All time works in H/C Type)
The parameter to set divide each zone of 3 PID. It is setting for Number 1 in
‘IN.RL(mV, IN.SL when input V-Sensor)~ 1.RP, and Number 2 in ‘1.RP ~ 2.RP,
Number 3 in ‘2.RP ~ IN.RH (mV, IN.SH when input V-Sensor).
※ The contents of PID Group number 2 is the same as PID Group number 1.
The parameter to set Proportional operation for PID control at cooling side in
H/C type. Setting range of ‘1.Pc’ is0.0(when ON/OFF control),
0.1 ~ 999.9%’.
Its initial setting is ’10.0%’.
The parameter to set Integral time for PID control at cooling side in H/C type.
Setting range of ‘1.Ic’ is ‘OFF, 1 ~ 6000 sec.
Its initial setting is ’120 sec’.
The parameter to set Derivative time for PID control at cooling side in H/C type.
Setting range of ‘1.Dc’ is ‘OFF, 1 ~ 6000 sec.
Its initial setting is ’30 sec’.
The parameter to set DEAD BAND which is the are where the controller does
not output from either the heating or cooling side.
※ The operation for Heat/Cool is shown as Fig 6.7.8
The parameter to set divide each zone of 3 PID. It is setting for Number 1 in
‘IN.RL(mV, IN.SL when input V-Sensor)~ 1.RP, and Number 2 in ‘1.RP ~ 2.RP,
Number 3 in ‘2.RP ~ IN.RH (mV, IN.SH when input V-Sensor).
The parameter to set hysteresis width of zone PID.
The parameter to set deviation of deviation PID.
The parameter to set the integration time for PID control.
Setting ranges of ‘1.I’ are ‘OFF’,’1 ~ 6000 sec’.
Its initial setting is 120 sec.