S&A CW-5000AG - Alarm Function; Thermostat Parameters List

S&A CW-5000AG
11 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
compressor, flow alarm, over
temperature alarm
compressor, flow alarm, over
temperature alarm
compressor, flow alarm, over
temperature alarm
Pump Power
0.03KW
0.03KW
0.03KW
Maximum Flow
10L / min
10L / min
10L / min
Maximum Pumping
Lift
10M
10M
10M
Inlet and Outlet
External Dia.: 10mm brass
connector
External Dia.: 10mm brass
connector
External Dia.: 10mm brass
connector
Alarm function
E1
E2
E3
E4
E5
Over high room
temperature
Over high water
temperature
Over low water
temperature
Room temperature
sensor failure
Water temperature
sensor failure
Remark:
When alarm occurs, the error code and the temperature will be alternately displayed.
In alarming state, the alarm sound could be suspended by pressing any button, but the alarm display remains until the alarm
condition is eliminated.
Thermostat parameters list
Order
Code
Project Setting
Range
Factory
Setting
Notes
1
F0
Temperature setting
F9 F8
25
Constant temperature control effecting
2
F1
Temperature difference values
-15 - +5
-2
Intelligent control effecting
3
F2
Cooling hysteresis
0.1 3.0
0.8
4
F3
Way of control
0 - 1
1
1: intelligent
0: constant temperature
5
F4
Alarm for over high water temperature
1 - 20
10
6
F5
Alarm for over low water temperature
1 - 20
15
7
F6
Alarm for over high room temperature
40 - 50
45
8
F7
Password
00 - 99
8
9
F8
The allowed highest water temperature
F0 - 40
30
10
F9
The allowed lowest water temperature
1 F0
20