RMUP-300 Series
8
21
Standby antifreeze
enabled
0-Disable1-Enable
0
40067
22
Constant temperature
standby temperature
difference
0.0~10.0
0.1
40068
23
State transition delay
0~99
Second
20
40069
PID
Parameter
24
PID enable
0-Disable1-Enable
1
40070
25
PID output cycle
0.1~40.0
Second
10.0
40071
26
PID integral period
1~50
Second
10
40072
27
PID-KP
0~100
10
40073
28
PID-KI
0~100
1
40074
29
PID-KD
0~100
2
40075
Sensor
Parameter
30
Temp. sensor selection
0-5K1-10K
10K
40076
31
Flow sensor selection
0-Switch type
1- Analog type
1
40077
32
Flow sensor coefficient
0.1~60.0
13.0
40078