RMUP-300 Series
7
2Parameter setting table
Parameter
category
Order
Parameter name
Range
Unit
Factory
setting
Parameter
address
User
Parameter
1
Temperature setting
-20.0~70.0
25.0
40047
2
Heating difference
-5.0~8.0
0.3
40048
3
Compressor starting
temperature difference
0.1~8.0
0.8
40049
4
Compressor stop
temperature difference
0.0~8.0
5.0
40050
5
Following temperature
difference
-20.0~20.0
0
40051
Administrator
Parameter
6
Start/stop mode
0-Power on hold
1-Power on start
2- Power on standby
1
40052
7
Upper temp. limit alarm
25.0~80.0
45.0
40053
8
Lower temp. limit alarm
-25.0~20.0
5.0
40054
9
Lower flow rate limit
protection
0~90.0
L/Min
0.5
40055
10
Flow Switch type
0-normally open type;
1-normally closed type
1
40056
11
Alarm output type
0-normally open type;
1-normally closed type
1
40057
12
Flow detection delay
0~300
Second
10
40058
13
Comp start delay
10~600
Second
60
40059
14
System start/stop mode
0-Local control
1-Remote control
2-Local and remote
control
0
40060
15
DI1 input function
0-Water level switch
1-Compressor overload
2-Pump overload
3-Power failure
4-Remote linkage
0
40061
16
DI1 input type
0-normally open type;
1-normally closed type
0
40062
17
Mode selection
0-constant temperature
mode
1-intelligent mode
0
40063
18
Model selection
0-Single cold type
1-Thermostatic type
1
40064
19
Temperature following
the upper limit
25.0~45.0
30.0
40065
20
Temperature following
the lower limit
0.0~25.0
20.0
40066