S&C Instruction Sheet 761-515 5
Safety Information
Location of Safety Labels and Tags
Reorder Information for Safety Labels
Location Safety Alert Message Description Number
A
DANGER
Electrocution Hazard G-6580-1
B
WARNING
Piercing Set Screws
G-10200
C
WARNING
Handle Operation G-4400R5
D
WARNING
Electrocution Hazard—Grounding Strap
G-6596
E
WARNING
Adjustment of Operating Mechanism
G-3578R1
This part is a tag that is to be removed and discarded after the switch is installed and adjusted.
D E
A
B
C
WARNING
INSTALLATION OF PIERCING SET SCREWS
(See illustrations on reverse side of tag)
1. Be sure that cutting tip of piercing set screw does not protrude through
the coupling body before installing operating pipe.
2. Install operating pipe section in coupling and finger tighten clamp bolt.
See Figure 1.
3. Adjust operating pipe. Then tighten clamp bolt.
4. Tighten piercing set screw, piercing the pipe, and continue turning until
firm resistance is felt. See Figure 2.
5. Make sure clamp bolt is tight.
Failure to properly install piercing set screws can cause slippage of
operating pipe, causing improper operation of switch, arcing, damage,
or electrical shock

Other manuals for S&C Alduti-Rupter

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C Alduti-Rupter and is the answer not in the manual?

S&C Alduti-Rupter Specifications

General IconGeneral
BrandS&C
ModelAlduti-Rupter
CategorySwitch
LanguageEnglish

Related product manuals