6 S&C Instruction Sheet 761-515
Safety Precautions
DANGER
Alduti-Rupter Switches operate at high voltage. Failure to observe these precautions will
result in serious personal injury or death.
Some of these precautions may differ from company operating procedures and rules. Where a
discrepancy exists, users should follow their company’s operating procedures and rules.
1. QUALIFIED PERSONS. Access to switches and
controls must be restricted only to qualified persons.
See “Qualified Persons” on page 2.
2. SAFETY PROCEDURES. Always follow safe operating
procedures and rules.
3. PERSONAL PROTECTIVE EQUIPMENT. Always use
suitable protective equipment such as rubber gloves,
rubber mats, hard hats, safety glasses, and flash
clothing in accordance with safe operating procedures
and rules.
4. SAFETY LABELS AND TAGS. Do not remove
or obscure any of the “DANGER, “WARNING,
CAUTION,” or “NOTICE” labels and tags. Remove tags
ONLY if instructed to do so.
5. ENERGIZED COMPONENTS. Always consider all
parts live until de-energized, tested, and grounded.
6. INTERRUPTER SWITCH POSITION. Always confirm
the Open/Close position of interrupter switches by
visually observing the position of the blades. Switches
may be energized from either side and with the blades
in any position.
7. MAINTAINING PROPER CLEARANCE. Always
maintain proper clearance from energized components.
8. OPERATION. Circuit making and breaking is involved
in the normal operation of this interrupter switch and as
a result, “partway” opening or closing is undesirable.
To operate, swing the operating handle through its full
travel vigorously and without hesitation. See page27.