Off: stop the unit.
Manual Reduced pressure / Manual Normal pressure: Setting manually selection.
Auto: Selection of set point is done according to time programming (see Programme schedule
section).
Advanced level
Occasionally, depending on the characteristics of the duct net (length and diameter) and also
depending on regulating elements (type of dampers and opening / closing times), It may be
necessary to modify the fans speed control output (Proportional and Integral bands).
To modify the proportional and integral bands, from the advanced parameters menu follow the
following sequence:
1- Access to system level
Temperature
Air control
Time sengs
Access rights
Log on
Log off
Change password
Log on
Enter password****
Actual level: None
Log on
Enter password ****
Actual level: None
Log on
Enter password ****
Actual level: Admin
To modify value
To change of digit
2- Adjust the COP parameters
Manual/Auto
Sengs
Configuraon
Access Rights
Temperature control
Pressure control
Alarm sengs
Pressure Ctrl. Supply
P.Band: 1000.0Pa
Acc-I: 20.0 s
Min.output: 20%
Change
parameters
Change
parameters
Pressure Ctrl. Supply
P.Band: 1000.0Pa
Acc-I: 20.0 s
Min.output: 20%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&P CADB/T-HE PRO-REG Series and is the answer not in the manual?

S&P CADB/T-HE PRO-REG Series Specifications

General IconGeneral
BrandS&P
ModelCADB/T-HE PRO-REG Series
CategoryHeating System
LanguageEnglish

Related product manuals