36
ENGLISH
The intervals are programmed day by day or copied by selecting either the same programming from
Monday to Friday and/or the same Saturday and Sunday and Holidays.
Holiday periods are to be selected at the end of the table (24 possible periods).
10. BOOST FUNCTION (Only available in CAV and COP modes)
By closing an external digital contact, it is possible to force the fan operation at normal speed for a
setted time. (30 mins. by default)
The speed corresponds to the normal pressure setpoint set in COP mode or to the normal airfl ow
specifi ed in CAV mode.
The Boost function can be activated, only when the unit is not within a timer period of normal speed.
In this case, even if boost is executed, the timer will start to count once the period of normal speed is
nished (the boost order gets delayed).