EasyManua.ls Logo

Sanyo CH3642 - Page 112

Sanyo CH3642
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I - 108
SM830082
1
2
3
4
5
1. Specifications
Cooling:
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
Heating:
Rating Conditions : Indoor Air Temperature 70 °F DB / 60 °F WB
Outdoor Air Temperature 47 °F DB / 43 °F WB
Full Load Conditions : Indoor Air Temperature 80 °F DB / — °F WB
Outdoor Air Temperature 45 °F DB / 35 °F WB
Indoor model: XH3642 / Outdoor model: CH3642
Cooling
Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.9 - 0.8 1.8 - 1.8 12.7 - 13.2 15.4 - 15.8
kW 0.20 - 0.16 0.36 - 0.34 2.79 - 2.70 3.35 - 3.20
Full load conditions
A 0.9 - 0.8 1.8 - 1.8 15.4 - 16.7 18.1 - 19.3
kW 0.20 - 0.16 0.36 - 0.34 3.43 - 3.41 3.99 - 3.91
Starting amperes A 1 - 1 2 - 2 95 - 86 98 - 89
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.7 - 0.6 1.8 - 1.8 15.7 - 16.9 18.2 - 19.3
kW 0.16 - 0.12 0.36 - 0.34 3.33 - 3.29 3.85 - 3.75
Full load conditions
A 0.7 - 0.6 1.8 - 1.8 14.2 - 15.6 16.7 - 18.0
kW 0.16 - 0.12 0.36 - 0.34 3.16 - 3.21 3.68 - 3.67
Starting amperes A 1 - 1 2 - 2 95 - 86 98 - 89

Table of Contents