EasyManua.ls Logo

Sanyo CH3642 - Automatic Fan Speed (Indoor Unit); (A)Cooling; (B)Heating

Sanyo CH3642
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
II - 5
SM830082
1
2
3
4
Section
5
2. Processes and functions
Fig. 4
2-3 Automatic Fan Speed (Indoor Unit)
(A) Cooling
By pressing the FAN SPEED button on the remote controller, the fan speed can be set at
one of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speed
will be automatically adjusted to the room temperature as the two charts shown below.
(B) Heating
Fig. 5
INDOOR FAN
SPEED
L
H
MM
H
1923_M_S
ROOM TEMP.
(deg)
SET TEMP.
+3
+2
+1
H
M
: High
: Middle
L : Low
Chart Explanations and notes
When the fan speed changes, it keeps the speed step for at least 3 minutes, even if the
temperature changes to another speed step during the time.
INDOOR FAN
SPEED H
L
M
M
H
1924_M_S
ROOM TEMP.
(deg)
SET TEMP.
–2
–4
H
M
: High
: Middle
L : Low
Chart Explanations and notes
When the fan speed changes, it keeps the speed step for at least 1 minute, even if the
temperature changes to another speed step during the time.

Table of Contents

Related product manuals