1. Specifications
MODEL No. XH3642
Source 230 - 208 VAC / 1 phase / 60 Hz
Remote controller (Option) RCS - SH80UA, WL
Controller P. C. B Ass'y CR - TH2442
Control circuit fuse 250 VAC, 3 A
Fan (Number … diameter) in. (mm) Turbo (1…17-7/16 (443))
Fan motor
Model SFG6X - 81A6P
Source 230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High) rpm 6 … 467
Nominal output W 60
Coil resistance BRW - WHT : 75.1 , ORG - YEL : 27.4
(Ambient temperature 68 °F) WHT - VLT : 6.7 , VLT - PNK : 42.7
VLT - ORG : 20.6 , YEL - BLK : 58.0
Safety device
Operating temperature Open °F266± 14.4
Close °F 174.2 ± 27
Run capacitor VAC, µF 440 V , 5 µF
Electronic expansion valve
Coil EKV - MOZS742E
Coil resistance (at 20°C) ORG - GRY : 46 , YEL - GRY : 46
RED - GRY : 46 , BLK - GRY : 46
Valve body HKV - 30D27
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … Fins per inch 2 … 14.9
Face area ft.
2
(m
2
) 8.20 (0.762)
Panel
Model No. PNR - XH3642
Auto louver motor MT8 - 3C
Auto louver motor … Rated V, W, rpm 240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F) 16.430 ± 8 %