SM830082
IV - 37
SM830082
4. Service procedures
(6) R.C. Address Setting Method
(“0” when shipped from factory)
1
ON
ON side
OFF side
2
0
R.C. address
R.C. address R.C. address
(S3 2P dip switch, green or blue) (S2 Rotary switch, Black)
00 auto address
Both OFF Set to 0
1
ON
10
position
20
position
ON side
: S2
: S3
OFF side
Refrigerant circuit address
(2P DIP switch, green or Blue)
Refrigerant circuit address (black)
Refrigerant circuit address
(factory setting = 0)
Outdoor control PCB
2093_C_I
2
0
A. ADD (S1):
Automatic address setting start button
Used for central control (link system)
and group control (Normally, not used)
CN006 (2P Black)
Outdoor unit R.C. address setting method
In case of group control or central control, set the R.C. address to 1, 2, 3, ... according to the No. of outdoor
units.