EasyManua.ls Logo

Sanyo CHDZ07263 - Page 81

Sanyo CHDZ07263
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 - 19
Trouble Diagnosis
3. W-3WAY ECO-i Alarm Codes
1
2
3
4
5
6
7
8
H31 Alarm
Alarm code H31
Alarm meaning HIC trouble alarm
Alarm conditions This alarm occurs when the microcomputer identifies a trouble signal (indicating abnormal HIC
temperature or other trouble) from the HIC.
Probable cause Overcurrent in HIC circuit, and resultant abnormal heating, caused by HIC failure
Check Check the power wiring and connector wiring. If the wiring and connectors are normal, use a
tester to measure the resistance between the compressor HIC power (HIC+) and ground (HIC–).
If there is a short circuit, there is an HIC malfunction.
Correction If an HIC failure is found, replace the PCB.
Example
Notes Turn OFF the power, and check the continuity of HIC+ and HIC– on the HIC PCB.
L04 Alarm
Alarm code L04
Alarm meaning Outdoor unit refrigerant system address duplication
Alarm conditions Communication by inter-unit control wiring was received that contained the same address as that
unit 5 times or more within 3 minutes.
Probable cause Incorrect outdoor system address settings
Check Check the system address settings again.
Correction Correct the system address settings.
Example
Notes Recovery from this alarm occurs automatically (when communication that contains the same
address as that unit is not received for 3 minutes after detection).
The HIC judges the current and temperature, and outputs the trouble signal. In general this
indicates trouble with the HIC itself.
HIC
-
HIC PCB
HIC
+
SM830183-003WAYECO-i.indb19SM830183-003WAYECO-i.indb19 2010/03/0311:14:562010/03/0311:14:56

Table of Contents

Related product manuals