3 - 20
Trouble Diagnosis
3. W-3WAY ECO-i Alarm Codes
1
2
3
4
5
6
7
8
L10 Alarm
Alarm code L10
Alarm meaning Outdoor unit capacity not set
Alarm conditions The outdoor unit capacity has not been set, or the setting is not allowed by the system.
Probable cause This alarm occurs because the capacity has not been set.
Check Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed
setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is
not set to “0” or to a capacity that is not allowed.
Correction If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it
correctly.
* After changing the setting, be sure to reset both the indoor and outdoor power.
Example
Notes The outdoor unit maintenance remote controller is required in order to set the capacity in the
outdoor unit EEPROM.
L17 Alarm
Alarm code L17
Alarm meaning Outdoor unit model mismatch
Alarm conditions This alarm occurs when a unit other than a R410A refrigerant model is connected.
Probable cause (1) A unit that uses R407C refrigerant, or a R22 model unit, was connected by mistake.
(2) The connected unit is correct, however the refrigerant type setting in the outdoor unit
EEPROM (item code 80) is incorrect.
Check (1) Check the refrigerant type at the connected unit.
(2) Use the outdoor unit maintenance remote controller and check the item code 80 refrigerant
type. If the setting is incorrect, change it to R410A.
Correction
Example
Notes The outdoor unit maintenance remote controller is required in order to set the refrigerant type in
the outdoor unit EEPROM.
SM830183-003WAYECO-i.indb20SM830183-003WAYECO-i.indb20 2010/03/0311:14:562010/03/0311:14:56