Control of W-ECO MULTI SYSTEM
3
TD831077
III - 48
c Select the zone and group No. which you want to set with ZONE and , (GROUP) buttons.
d Set the UNIT No. (Indoor unit address) with FAN SPEED and FLAP buttons according to the zone registration
table.
R.C. No. FAN SPEED button
Indoor unit No. FLAP button
e Press the SET button.
GROUP No. turns ON and UNIT No. (Indoor unit address) changes from flashing to ON state.
UNIT No. is registered to selected ZONE No. and GROUP No..
If you make mistake, then press the CL button and re-select the ZONE, GROUP and UNIT No.
2. Optional Controller (system controller)
For example, in case of left
Zone 3, GROUP No. 7
UNIT No. (Indoor unit address) 2-8
: UNIT No. 2–8 is registered to
Zone 3–GROUP 7.
f Register the other UNIT No. in the same way by following the above steps c to e.
g Finally, complete the registration by pressing the TEST / CHK button.
SETTING
changes from flashing to OFF state.
SET CL
MODE
FAN SPEED
FLAP
SET TEMP.
SELECT
CENTRAL
CTRL
GROUP
ZONE
R.C. No.
UNIT No.
No.
CODE
ZONE
19
2
3
4
6
7
ON
OFF
TEST / CHK
ALL / ZONE / GR
SETTING
835_8132