II - 19
2
TD831077
Design of W-ECO MULTI SYSTEM
3. Electrical Wiring
3-1. General precautions on wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring
closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each
unit, and a power supply disconnect and circuit breaker
for overcurrent protection should be provided in the
exclusive line.
(3) To prevent possible hazards from insulation failure, the
unit must be grounded.
(4) Each wiring connection must be done in accordance
with the wiring system diagram. Wrong wiring may
cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
(A) Power supply Power supply terminal base**
Wire size Max. length Capacity Max. wire size
SPW-C1503GDYH8 10 mm
2
41 m 60 A 80 A 22 mm
2
(AWG #4)*
SPW-C1903GDYH8 10 mm
2
33 m 80 A 80 A 22 mm
2
(AWG #4)*
SPW-C703GDCH8 6 mm
2
45 m 45 A 50 A 14 mm
2
(AWG #6)*
SPW-C903GDCH8 6 mm
2
39 m 50 A 50 A 14 mm
2
(AWG #6)*
SPW-CR1503GDYH8 10 mm
2
36 m 60 A 80 A 22 mm
2
(AWG #4)*
SPW-CR1903GDYH8 10 mm
2
35 m 80 A 80 A 22 mm
2
(AWG #4)*
SPW-CR703GDCH8 6 mm
2
43 m 50 A 50 A 14 mm
2
(AWG #6)*
SPW-CR903GDCH8 6 mm
2
37 m 50 A 50 A 14 mm
2
(AWG #6)*
Time delay fuse or
circuit capacity
R22
R407C
3-2. Recommended wire length and wire diameter for power supply system
Outdoor unit * AWG = American Wire Gauge
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your
LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as
follows:
The remote control wiring and the inter-unit control
wiring should be wired apart from the inter-unit power
wiring.
Use shielded wires for inter-unit control wiring between
units and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged,
it must be replaced by a repair shop appointed by the
manufacture, because special purpose tools are
required.
**
With ring type wire terminal.
NOTE
Control wiring
Indoor unit
Time delay fuse or
circuit capacity
Type
(B) Power supply Power supply terminal base
2.5 mm
2
Capacity Max. wire diameter
AS, SL, S, X, K, T, U, F, FM
Max. 100 m 10 A 25 A
5.5 mm
2
(AWG #10)*
D Max. 60 m 10 A 50 A
14 mm
2
(AWG #6)*
DR763 / 963 Max. 50 / 30 m 10 A 50 A
14 mm
2
(AWG #6)*
(C) Inter-unit control wiring (D) Remote control wiring (E) Control wiring for group control
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18) 0.75 mm
2
(AWG #18)
Use shielded wiring
Max. 1,000 m Max. 500 m (Total) Max. 500 m (Total)