MODEL No. Outdoor Unit SPW – CR703GVH8
POWER SOURCE 380 - 400 - 415 V / 3 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 22.4 25.0
BTU / h 76,400 85,300
Air circulation (Hi) m
3
/min(cu. ft/min) 155 (5,470)
ELECTRICAL RATINGS
Voltage rating V 380 - 400 - 415
Available voltage range V 342 - 456
Running amperes A 15.8 - 15.2 - 14.9 14.2 - 13.7 - 13.5
Max. running amperes* A 20.6 - 19.6 - 19.2 —
Power input kW 9.45 - 9.50 - 9.56 8.52 - 8.57 - 8.62
Max. power input* kW 12.1 - 12.2 - 12.4 —
Power factor % 90.9 - 90.2 - 89.3 91.2 - 90.3 - 88.8
C.O.P W/W 2.37 - 2.36 - 2.34 2.93 - 2.92 - 2.9
Compressor locked rotor amperes A 51 - 53 - 55
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment kg R407C - 9.5
Refrigerant control Electronic expansion valve
Operation sound (Hi) dB-A 58
Compressor Super power control twin rotary compressor
Color (Approximate value) Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length m(ft.) 100 (328)
Limit of elevation difference m(ft.) Outdoor unit is higher than indoor unit : 50 (165)
between the two units Outdoor unit is lower than indoor unit : 30 (100)
Refrigerant tube Narrow tube mm (in) 12.7 ( 1 / 2 )
outer diameter Wide tube mm (in) 25.4 ( 1 )
Refrigerant tubing kit / joint kit Optional
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Unit dimensions Height mm(in) 1,218 (48 - ) 1,351 (53 - 1 / 4)
Width mm(in) 883 ( 34 - 3 / 4) 1,047 ( 41 - 1 / 4)
Depth mm(in) 883 (34 - 3 / 4) 1,005 ( 39 - 5 / 8)
Net weight kg(lb) 231 ( 510 )
Shipping weight kg(lb) 234 ( 516 )
Shipping volume m
3
(Cu. ft.) 1.42 ( 50.1 )
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °C DB / 19.0 °C WB , Outdoor air temperature 35 °C DB
Heating: Indoor air temperature 20 °C DB , Outdoor air temperature 7 °C DB / 6 °C WB
* Full load conditions at Indoor / outdoor capacity ratio 130 %
Cooling: Indoor air temperature 32 °C DB / 22.5 °C WB , Outdoor air temperature 43 °C DB / 25.5 °C WB