ECO MULTI SYSTEM Unit Spesifications
SM830063
I-8
1
1. Outdoor Unit
Unit specifications (F)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °C DB / 19.0 °C WB , Outdoor air temperature 35 °C DB
* Full load conditions at Indoor / outdoor capacity ratio 130 %
Cooling: Indoor air temperature 32 °C DB / 22.5 °C WB , Outdoor air temperature 43 °C DB / 25.5 °C WB
MODEL No. Outdoor Unit SPW – CR703GV8
POWER SOURCE 380 - 400 - 415 V / 3 phase / 50Hz
PERFORMANCE Cooling
Capacity kW 22.4
BTU / h 76,400
Air circulation (Hi) m
3
/min(cu. ft/min) 155 (5,470)
ELECTRICAL RATINGS
Voltage rating V 380 - 400 - 415
Available voltage range V 342 - 456
Running amperes A 15.8 - 15.2 - 14.9
Max. running amperes* A 20.6 - 19.6 - 19.2
Power input kW 9.45 - 9.50 - 9.56
Max. power input* kW 12.1 - 12.2 - 12.4
Power factor % 90.9 - 90.2 - 89.3
C.O.P W/W 2.37 - 2.36 - 2.34
Compressor locked rotor amperes A 51 - 53 - 55
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment kg R407C - 9.5
Refrigerant control Electronic expansion valve
Operation sound (Hi) dB-A 58
Compressor Super power control twin rotary compressor
Color (Approximate value) Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length m(ft.) 100 (328)
Limit of elevation difference m(ft.) Outdoor unit is higher than indoor unit : 50 (165)
between the two units Outdoor unit is lower than indoor unit : 30 (100)
Refrigerant tube Narrow tube mm (in) 12.7 ( 1/ 2 )
outer diameter Wide tube mm (in) 25.4 ( 1 )
Refrigerant tubing kit / joint kit Optional
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Unit dimensions Height mm(in) 1,218 (48 ) 1,351 (53 - 1 / 4)
Width mm(in) 883 (34 - 3 / 4) 1,047 (41 - 1 / 4)
Depth mm(in) 883 (34 - 3 / 4) 1,005 (39 - 5 / 8)
Net weight kg(lb) 229 ( 505 )
Shipping weight kg(lb) 229 ( 505 )
Shipping volume m