Instruction Manual for Electrobloc EBL 262-4
5
Date: 08.07.2019
8110265 BA / EN
1
Fig. 1 Battery selector switch
"
Set the battery selector switch (fig. 1, pos. 1) to the correct position using
a thin object (such as a ballpoint pen):
F Lead-gel battery: Set the battery selector switch to ”Lead-gel”.
F Lead-acid battery: Set the battery selector switch to ”Lead-acid”.
" Start up the system as described in section 3.1.
3.3 System faults
A fault in the power supply system is usually caused by a blown fuse.
Please contact our customer service department if you cannot rectify the
fault using the following table.
If this is not possible, e.g. if you are abroad, you can have the electrobloc
repaired at a specialist workshop. Please note that the warranty will become
void if incorrect repair work is carried out. Schaudt GmbH shall not accept
liability for any damages resulting from such repairs.
The following functions are protected by a polyswitch fuse:
F 12 V indicator
F Battery 1
F Output D+
If a fault occurs here, the electrobloc must be switched off for approx. 1 min.
and be disconnected from the 230 V mains. The polyswitch fuses reset au-
tomatically during this period.
Fault Possible cause Remedy
Living area battery is not
No mains voltage Switch on the automatic
charged during 230 V
circuit breaker in the
constantly below 13.3 V)
voltage
Too many consumers are
switched on
Switch off consumers not
required
Defective electrobloc Contact the customer
service department
Living area battery is
overcharged during 230 V
operation (battery voltage
constantly above 14.5 V)
Defective electrobloc Contact the customer
service department
Starting up the system
Flat vehicle fuses
Polyswitch fuses