10/22 Ref. GPAO : 33502017201_1_1
Generating set without air preheating option
Sequence Screen display LED status
o Starting
Flashing:
p Generating set runs at a stable speed
Permanently lit:
In this case, charging is possible.
Note:
The MICS Nexys does not control opening and closing commands for the N/E reversing switch.
In this case, and if the N/E switch is a third-party component, it must have its own control mechanism for the N/E switching
components.
3.2.2 Stopping the generating set
When the power is restored (controlled by the SDMO switch), there is a time delay. After this (120 seconds), the external
command disappears, the "emergency" switch is triggered and the "normal" switch is deactivated.
When the external command disappears, the "AUT" pictogram continues to flash followed by the cooling delay.
The LED
remains lit.
The following screen appears.
When this is complete (120 seconds), the generating set switches off and the "AUT" pictogram goes out.
(1) The emergency switch is controlled by the reversing switch control.
(2) The motor cooling delay is integrated into the Nexys module.