Smart valve positioner
SP740 Series
Control is possible but it indicates when it can be happened abnormal operation or
precsion degree can be degraded.
▶ Reduce discharge air pressure
▶ Replace with large actuator size .
▶ Re-execute auto calibration.
▶ Re-set air regulator setting
pressure to normal pressure.
▶ Check air pressure status.
▶ Indicates that PV is 1% and more
far from the deadzone or does not
move and the state lasts a minute
▶ Indicates that SV and PV's tolerance
is over 5% and it continues
▶ Indicates that valve friction is
too large or input pressure is
▶Check in the error of View Mode
Warning contents and cause
▶ Indicates that actuator size is
▶ Indicates that FULL OPEN / FULL CLOSE
time is shorter than 0.8 second.
38/40
▶Check signal generator out put
and adjust it within the available
operation range.
* Check the error in VIEW MODE.
far from the deadzone or does not
move and the state lasts a minute
▶ Indicates that SV signal is
LOW : 300 M , HIGH : 4000 and more
38/40