EasyManua.ls Logo

Sel SEL-487B - Functional Overview

Sel SEL-487B
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SEL-487B Data Sheet Schweitzer Engineering Laboratories, Inc.
2
The relay records a wide range of system events with sampling rates as fast as 8 kHz, and as much as
24 seconds of data per COMTRADE compliant event report.
Parallel Redundancy Protocol (PRP) provides seamless recovery from any single Ethernet network
failure, in accordance with IEC 62439-3. The Ethernet network and all traffic are fully duplicated with
both copies operating in parallel.
IEEE 1588, Precision Time Protocol version 2 provides high-accuracy timing over an Ethernet net-
work.
Time-domain link (TiDL) technology allows for remote data acquisition through use of the SEL-2240
Axion. The Axion provides remote analog and digital data over an IEC 61158 EtherCAT TiDL net-
work. This technology provides very low and deterministic latency over a fiber point-to-point architec-
ture. The SEL-487B-1 Relay can receive fiber links from as many as eight Axion remote data
acquisition nodes.
Functional Overview
Figure 1 SEL-487B Relay Basic Functions in a Double-Bus Application
ANSI NUMBERS/ACRONYMS AND FUNCTIONS
16 SEC Access Security (Serial, Ethernet)
27/59 Over- and Undervoltage
50 Overcurrent
50BF Breaker Failure Overcurrent
51 Time-Overcurrent
85 RIO SEL M
IRRORED
B
ITS
Communications
87 Current Differential
DFR Event Reports
HMI Operator Interface
LGC Expanded
SEL
OGIC
Control Equations
MET High-Accuracy Metering
RTU Remote Terminal Unit
SER Sequential Events Recorder
ADDITIONAL FUNCTIONS
SBM Station Battery Monitor
1
Copper or Fiber Optic * Optional Feature
ADDITIONAL FEATURES
Open CT Detection
Three Independent Check Zones
Disconnect Status and Monitoring Logic for 60 Disconnects
Single-Relay Application: 2 Three-Phase Zones for as many as 7 Terminals
Two-Relay Application: 3 Three-Phase Zones for as many as 10 Terminals
Three-Relay Application: 6 Single-Phase Zones for as many as 21 Terminals
4
EIA -232
2
Ethernet
1
*
16
S
E
C
27
59
85
RIO
DFR
HMI
LGC
MET SBMRTU SER
1
IRIG-B
SEL-487B
52- 1
3
52- 2
3 3 3
52- 3
3
52-4
33
52-5
52-6
3 3
50 50 50 50 50 50 50
51 51 51 51 51 51 51
50BF 50BF 50BF 50BF 50BF 50BF 50BF
8787
Zone 1
Zone 1
Zone 2
Zone 2
PT898989
8989
8989
Tie Breaker
TiDL Time-Domain Link Remote Data Acquisition

Related product manuals