5.2.14 IO – Analog inputs -View
To view analog inputs, use the Analog Inputs – View Screen.
Figure 19: Analog Inputs - View Screen
This screen displays the 4-20mA values for the analog inputs. Press the escape button when
finished viewing to return to the previous screen.
No changes can be made from this screen.
5.2.15
IO – Analog inputs - Cal
To calibrate analog inputs, use the Analog Inputs – Cal Screen.
Figure 20: Analog Inputs - Cal Screen
Use this screen when you wish to calibrate the 4-20mA values for the analog inputs.
To calibrate analog inputs:
1. Supply 4.00 mA from a calibrated source to the desired input.
2. Touch the “Press to Cal” area of the screen below the input you wish to calibrate.