Switched PDU
Installation and Operations Manual Advanced Operations 105
Setting the SNMP v3 read-only (RO) authentication password:
The Set SNMP RO Auth Password command sets the SNMP v3 RO authentication password. A valid authentication
password can be set to any value between 1-40 characters. A blank password will clear the string.
To set the RO authentication password:
At the Switched CDU: prompt, type set snmp v3 roauthpass, and press Enter.
Setting the SNMP v3 read-only (RO) privacy type :
The Set SNMP RO Priv Type command sets the SNMP v3 RO privacy type.
To set the RO privacy type:
At the Switched CDU: prompt, type set snmp v3 roprivtype, followed by none or des, and press Enter.
Setting the SNMP v3 read-only (RO) privacy password:
The Set SNMP RO Priv Password command sets the SNMP v3 RO privacy password. A valid privacy password can
be set to any value between 1-32 characters. A blank password will clear the string
To set the RO privacy password:
At the Switched CDU: prompt, type set snmp v3 roprivpass, and press Enter
Setting the SNMP v3 read-write (RW) username :
The Set SNMP RW Username command sets the read-write username for SNMP v3. A valid username can be set to
any value between 1-32 characters.
To set the RW username:
At the Switched CDU: prompt, type set snmpv3 rwusername, and press Enter.
NOTE: You can set a blank username but doing so will clear the string and disallow any read-write user access.
Setting the SNMP v3 read-write (RW) authentication type :
The Set SNMP RW Auth Type command sets the SNMP v3 RW authentication type.
To set the RW authentication type:
At the Switched CDU: prompt, type set snmp v3 rwauthtype, followed by none or md5, and press Enter.
Setting the SNMP v3 read-write (RW) authentication password:
The Set SNMP RW Auth Password command sets the SNMP v3 RW authentication password. A valid authentication
password can be set to any value between 1-40 characters. A blank password will clear the string
To set the RW authentication password:
At the Switched CDU: prompt, type set snmp v3 rwauthpass, and press Enter.
Setting the SNMP v3 read-write (RW) privacy type :
The Set SNMP RW Priv Type command sets the SNMP v3 RW privacy type. A valid password can be set to any
value between 1-40 characters.
To set the RW privacy type:
At the Switched CDU: prompt, type set snmp v3 rwprivtype, followed by none or des, and press Enter.
Setting the SNMP v3 read-write (RW) privacy password:
The Set SNMP RW Priv Password command sets the SNMP v3 RW privacy password. A valid privacy password can
be set to any value between 1-32 characters. A blank password will clear the string
To set the RW privacy password:
At the Switched CDU: prompt, type set snmp v3 rwprivpass, and press Enter.