Switched PDU
Installation and Operations Manual Advanced Operations 107
Setting the Get/Set community strings:
The Switched CDU supports two SNMP community strings that provide varying levels of access to objects defined in
the Sentry3 MIB.
Community strings can be 1 to 24 characters.
Setcomm:
The Setcomm string provides read-write access to sentry3 MIB objects. The default Setcomm string is blank.
To set the Setcomm community string:
At the Switched CDU: prompt, type set snmp setcomm, followed by the string and press Enter.
Getcomm:
The Getcomm string provides read-only access to sentry3 MIB objects. The default Getcomm string is “public”.
To set the Getcomm community string:
At the Switched CDU: prompt, type set snmp getcomm, followed by the string and press Enter.
Setting the SNMP SysName:
The Set SNMP SysName command is used to set the SNMP MIB-II SysName object.
To set the SysName object:
At the Switched CDU: prompt, type set snmp sysname, followed by the object name and press Enter.
Setting the SNMP SysLocation:
The Set SNMP SysLocation command is used to set the SNMP MIB-II SysLocation object.
To set the SysLocation object:
At the Switched CDU: prompt, type set snmp syslocation, followed by the object location and press Enter.
Setting the SNMP SysContact:
The Set SNMP SysContact command is used to set the SNMP MIB-II SysContact object.
To set the SysContact object:
At the Switched CDU: prompt, type set snmp syscontact, followed by the object contact and press Enter.