Switched PDU
Installation and Operations Manual Operations 69
To set the tower serial number:
At the Switched CDU: prompt, type set tower prodsn, followed by the absolute tower name, and the tower serial
number. Press Enter.
Example
The following command sets the serial number for tower .A to ‘AA06F011157’:
Switched CDU: set tower prodsn .a AA06F011157<Enter>
Setting the tower model number:
The Set Tower Model command is use to set the product model number.
NOTE: If set at the factory, you cannot edit the model number.
To set the tower model number:
At the Switched CDU: prompt, type set tower model, followed by the absolute tower name, and the tower model
number. Press Enter.
Example
The following command sets the model number for tower .A to ‘CW-8H1-C20’:
Switched CDU: set tower prodsn .a CW-8H1-C20<Enter>
Setting the tower AC or DC voltage type:
The Set Tower command is used to set the product input AC or DC voltage type.
NOTE: If set at the factory, you cannot edit the voltage type.
To set the tower AC/DC voltage type:
At the Switched CDU: prompt, type set tower, followed by ac or dc, and the absolute tower name. Press Enter.
Example
The following command sets the AC/DC voltage type for tower .A to AC:
Switched CDU: set tower ac.a<Enter>
Setting the tower AC voltage type:
The Set Tower 3phase command is used to set the product input AC voltage type.
NOTE: If set at the factory, you cannot edit the voltage type.
To set the tower AC voltage type:
At the Switched CDU: prompt, type set tower 3phase, followed by the absolute tower name and yes or no. Press
Enter.
Example
The following command sets the AC voltage type for tower .A to non-3-phase:
Switched CDU: set tower 3phase.a no<Enter>