82 Operations Switched PDU
Installation and Operations Manual
To set a blank EnergyWise secret:
A blank secret is acceptable.
At the Switched CDU: prompt, type set energywise secret, do not type in the Secret field, and press Enter twice (to
bypass the Secret field and then VerifySecret field.)
Example of a blank secret
Switched CDU: show energywise
EnergyWise Configuration
Endpoint: Enabled *
Port: 666
Domain: (undefined)
Refresh Rate: 60
Secret: (Blank)
Command successful
To set the EnergyWise refresh rate:
The EnergyWise refresh rate is the rate (in seconds) at which new information is pushed to the EnergyWise manager.
Valid range is 30-600 seconds; default is new data sent to the EnergyWise manager every 3 minutes.
At the Switched CDU: prompt, type set energywise refresh, followed by a rate (in seconds) from 30-600, and press
Enter.
Viewing Cisco EnergyWise network parameters:
NOTE: A change in any value (shown in the example below) requires a restart of the system.
To view EnergyWise network parameters:
At the Switched CDU: prompt, type show energywise, and press Enter.
Example
Switched CDU: show energywise
EnergyWise Configuration
Endpoint: Enabled*
Port: 666
Domain: <undefined>
Refresh Rate: 55
Secret: ********
Command successful