Fault/error table
Operating Instructions – MOVIMOT
®
flexible
253
Subfault: 46.50
Description: Warning
Response: Warning with self-reset
Cause Measure
Safety card signals subcomponent fault of the
type "Warning".
For the exact cause of the fault and for informa-
tion on how to correct the cause of the problem,
refer to the fault reported by the subcomponent
(index 8365.3).
Subfault: 46.51
Description: Fault
Response: Emergency stop + output stage inhibit with self-reset
Cause Measure
Safety card signals subcomponent fault of the
type "Standard fault".
For the exact cause of the fault and for informa-
tion on how to correct the cause of the problem,
refer to the fault reported by the subcomponent
(index 8365.3).
Subfault: 46.52
Description: Critical fault
Response: Output stage inhibit with self-reset
Cause Measure
Safety card signals subcomponent fault of the
type "Critical fault".
– For the exact cause of the fault and for informa-
tion on how to correct the cause of the problem,
refer to the fault reported by the subcomponent
(index 8365.3).
– If the jumper plug is plugged at terminal "X6",
remove the jumper plug.
8.6.33 Fault 51 Analog processing
Subfault: 51.1
Description: Analog current input 4mA limit
Response: Warning with self-reset
Cause Measure
Input current below 4mA. Check the input current.
8.6.34 Fault 52 Explosion protection function category 2
Subfault: 52.1
Description: Startup error
Response: Output stage inhibit
Cause Measure
No valid startup available. Perform startup.