2
AY-X36RU
AE-X36RU
PRODUCT SPECIFICATION
[1] SPECIFICATION
MODEL
ITEMS
INDOOR UNIT OUTDOOR UNIT
AY-X36RU AE-X36RU
Rated cooling capacity (Min. - Max.) Btu/h 33600 ( 7400
36000 )
Rated heating capacity (Min. - Max.) Btu/h 34600 ( 15000
36000 )
Moisture removal (at cooling) pints/h 7.4
Electrical data
Phase Single
Rated frequency Hz 60
Rated voltage V 208/230
Rated current Cool A 17
(Min.-Max.) Heat A 16.5
Rated input Cool W 4100 ( 450
4300 )
(Min.-Max.) Heat W 3800 ( 560
4300 )
Compressor
Type Rotary
Model TNB306FPGMC
Refrigerant system
Evaporator Aluminum Fin-copper tube type
Condenser Aluminum Fin-copper tube type
Control Expansion valve
Refrigerant
type R410A
oz. ( g ) 91.7 ( 2600 )
Noise level
(at cooling)
Turbo dB(A) 54
65
High 50
Low 44
Soft 38
Noise level
(at heating)
Turbo dB(A) 54
65
High 50
Low 44
Soft 38
Fan system
Drive Direct drive
Air ow quantity
(at cooling)
Turbo CFM(m3/min) 736 ( 20.8 ) 2589(73.3)
High 647 ( 18.3 )
Low 530 ( 15 )
Soft 412 ( 11.7 )
Air ow quantity
(at heating)
Turbo CFM(m3/min) 736 ( 20.8 ) 2589(73.3)
High 647 ( 18.3 )
Low 530 ( 15 )
Soft 412 ( 11.7 )
Fan Cross ow fan Propeller fan
Connections
Refrigerant coupling Flare type
Refrigerant tube size (Gas line ) inch (mm) 5/8 (16)
Refrigerant tube size (Liquid line ) inch (mm) 1/4 ( 6.35 )
Maximum length ft ( m ) 98.4 ( 30 )
Maximum charge-less length ft ( m ) 24.6 ( 7.5 )
Maximum height difference
ft ( m ) 32.8 ( 10 )
Additional charge oz./ft ( g/m ) 0.5 ( 50 )
Drain pipe O.D. inch (mm) 5/8 (16 )
Others
Safety device
Compressor: Thermal protector
Pressure switch
Fuse, Micro computer control
Air llters Polypropylene net (Washable)
Net dimensions
Width
Height
Depth
inch
(mm)
53-1/7
12-5/6
10
 
( 1350
326
253 )
38-4/7
31-1/9
16-4/5
 
( 980
790
427 )
Net weight lb. (kg) 41.9 ( 19 ) 161 ( 73 )
NOTE: Test conditions are based on AHRI 210/240. ( Refrigerant piping length : 25ft [7.6m] )
* : Voltage is 230V