Please note that programming the volume by setting the 0000 value, means programming 10.000,
while setting the AA00 value for the divider means programming the divider as 100.
You can treat maximum 70.000 liters water with the SIATA Hall effect liter counter by
programming 10.000 liters for the treatable volume and AA98 for the divider.
If you use a counter issuing one impulse every liter (or cubic meter), the maximum treatable volume
will be 1.000.000 liters (or cubic meters) if you set to 10.000 liters the treatable volume and to
AA00 the divider (corresponding to 100 impulses every liter or cubic meter). Please note that,
because of the Reed counters characteristics, we recommend not to use 1imp./1m3 or similar
counters.
6.7 – Installing the probe.
The conductivity probe is the most important element of Aqua Ionic and its installation must be
performed with the highest care. A screened cable is always the best choice to connect the
controller to the probe. This choice is compulsory when the distance between the controller and the
probe is over 2 meters and/or when the environment where the controller is being installed is
subject to strong electromagnetic interferences.
Nonetheless, it is possible to use normal cables if the distance between the controller and the probe
is short or if there are not great electric interference sources in the immediate neighborhoods.
In any case, it is advisable not to wire the probe cable near power cables.