At altitudes up to 2,000 m
abo
ve sea level … 3,000 m
above sea level
–25 °C … +50 °C
At altitudes 3,000 m above sea
level … 4,000 m above sea level
–25 °C … +45 °C
Storage temperature –25 °C … +70 °C
Air humidity 10% … 95%, non-condensing
Operating altitude Max. 4,000 m above sea level
Mechanical strength
Vibration resistance 5 Hz … 200 Hz / 1 g (EN 60068-2-6)
Shock resistance, single shock 15 g, 11 ms (EN 60068-2-27)
Operating data
Protection class III (EN 61140)
Immunity to interference EN 61000-6-2
Emitted interference EN 61000-6-4
Connections
Connection type Spring terminals
CP
Uc2: RJ45 female connector
Wire cross-section Single wire or fine-stranded wire: 0.14 mm² … 1.5 mm²
F
ine-stranded wire with ferrule:
a) with plastic ferrule max. 1.0 mm²
b) without plastic ferrule max. 1.0 mm²
AWG according to UL/CSA: 26 … 14
For UL and CSA applications:
Use copper conductors only min. rated for 85°C.
Network cable requirements
T
ype: 100Base-TX
Cables with RJ45 connections
Twisted pair Ethernet cable, maximum length 100 m
in accordance with EN 50173
Use of wire pairs 1/2 and 3/6
Shielded cables
Cat 5 STP or higher
Housing
Enclosure rating IP20 (EN 60529)
Contamination rating 2 (IEC 61010-1)
Control device type Open device (IEC 61010-2-201)
Weight (± 5%) CPUc1: 277 g
CP
Uc2: 282 g
Voltage supply (A1 / A2)
T
able 141: Voltage supply
Supply voltage U
B
+24 V DC
Tolerance of supply voltage –30% / +25% (16.8 V … 30 V)
Type of supply voltage PELV or SELV
T
he supply current must be limited externally to max. 8 A
– either by the voltage supply unit used, or by means of
a fuse.
Max. power loss CPUc1: 6.2 W
CP
Uc2: 6.3 W
13 TECHNICAL DATA