Operating Instructions PBS
42 ©SICKAG•Germany•Allrightsreserved•Subjecttochangewithoutnotice8013154/U275/2010/02/01
SICK-specic
Index
(dezimal)
Name Format Access Range Remark
70 OU2
8 Bit
enumerated
R/W
0=„Hno“:Hysteresis
mode (SP/RP) no
1=„Hnc“:Hysteresis
mode (SP/RP) nc
2=„Fno“:Window
mode (FH/HL) no
3=„Fnc“:Window
mode (FH/HL) nc
„no“ = „normally open“,
„nc“=„normallyclosed"
72 UNIT
8 Bit
Enumeration
R/W
0 = bar
1 = MPa
2 = kPa
3 = PSI
4 = kg/cm²
Thisparameterdenesthepressuremeasurementunitandthephysical
unitofthelocaldisplay.AftersettingthisparameterthevaluesforMBA
andMBEhavetobereadagainsincethesevaluesdependuponthe
pressure unit.
73 HI
16 Bit
unsigned
R 0…10000 Maximum pressure that was applied at the pressure switch for diagnosis.
74 LO
16 Bit
unsigned
R 0…10000 Minimum pressure that was applied at the pressure switch for diagnosis.
77 DS2
16 Bit
unsigned
R/W 0…50000(50s) Switch-ondelayofQ2inms.
78 DR2
16 Bit
unsigned
R/W 0…50000(50s) Switch-offdelayofQ2inms.
80 DISP
8 Bit
Enumeration
R/W
0 = 1 Hz
1 = 2 Hz
2 = 5 Hz
3 = 10 Hz
Sets the refresh cycles of the display.
240 MBA
32 Bit IEEE 754
oat
R
Theprocessvalue“PressureValue”islinearizedsuchthatavalueof
1000 corresponds to the lower end of the measuring range (MBA) and
thatavalueof9000correspondstotheupperendofthemeasuring
range(MBE).Pressurevalueslowerthanthelowerendofthemeasuring
rangearetransmittedas0.Pressurevaluesabovetheupperendofthe
measuring range are transmitted as 10000.
241 MBE
32 Bit IEEE 754
oat
R
Theprocessvalue“PressureValue”islinearizedsuchthatavalueof
1000 corresponds to the lower end of the measuring range (MBA) and
thatavalueof9000correspondstotheupperendofthemeasuring
range(MBE).Pressurevalueslowerthanthelowerendofthemeasuring
rangearetransmittedas0.Pressurevaluesabovetheupperendofthe
measuring range are transmitted as 10000.
7. Starting, operation