8013154/U275/2010/02/01 ©SICKAG•Germany•Allrightsreserved•Subjecttochangewithoutnotice 41
Operating Instructions PBS
SICK-specic
Index
(dezimal)
Name Format Access Range Remark
66
RP1/
FL1
16 Bit
unsigned
R/W 1000-8960
Correspondstotheprocessvalueatwhichtheswitchisdeactivated
(open,Q0V)ortothelowerlimitinthewindowmode.Incaseofthe
output being parametrized as „Hnc“ or „Fnc“ (normally closed), the logic
isinverted.ThevalueofRP1/FL1shallbeatleast40units(0,5%ofth
emeasuringrange)lowerthanthevalueofSP1orFH1,respectively.Ifthis
isnotthecase,RP1orFL1aresettothenearestpossiblevalue.
67 OU1
8 Bit
Enumeration
R/W
0=„Hno“:Hysteresis
mode (SP/RP) no
1=„Hnc“:Hysteresis
mode (SP/RP) nc
2=„Fno“:Window
mode (FH/HL) no
3=„Fnc“:Windowmode
(FH/HL) no
„no“ = „normally open“,
„nc“=„normallyclosed".
68
SP2/
FH2
16 Bit
unsigned
R/W 1040-9000
Correspondstotheprocessvalueatwhichtheswitchisactivated(closed,Q
+24V) or to the upper limit in the window mode. In case of the output being
parametrizedas„Hnc“or„Fnc“(normallyclosed),thelogicisinverted.The
valueofRP2/FL2shallbeatleast40units(0,5%ofthemeasuringrange)
lowerthanthevalueofSP2orFH2,respectively.Ifthisisnotthecase,RP2
orFL2aresettothenearestpossiblevalue.
75 DS1
16 Bit
unsigned
R/W 0…50000(50s) Switch-ondelayofQ1inms.
76 DR1
16 Bit
unsigned
R/W 0…50000(50s) Switch-offdelayofQ1inms.
69
RP2/
FL2
16 Bit
unsigned
R/W 1000-8960
Correspondstotheprocessvalueatwhichtheswitchisdeactivated(open,
Q0V)ortothelowerlimitinthewindowmode.Incaseoftheoutputbeing
parametrizedas„Hnc“or„Fnc“(normallyclosed),thelogicisinverted.The
valueofRP2/FL2shallbeatleast40units(0,5%ofthemeasuringrange)
lowerthanthevalueofSP2orFH2,respectively.Ifthisisnotthecase,RP2
orFL2aresettothenearestpossiblevalue.
7. Starting, operation
7. Starting, operation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK PBS Series and is the answer not in the manual?

SICK PBS Series Specifications

General IconGeneral
BrandSICK
ModelPBS Series
CategorySwitch
LanguageEnglish

Related product manuals