Operating Instructions PBS
40 ©SICKAG•Germany•Allrightsreserved•Subjecttochangewithoutnotice8013154/U275/2010/02/01
IO-Link-specic
Index
(dezimal)
Name Format Access Example Range Remark
16 Vendor Name R SICK AG RefertoIO-Linkspecication.
17 Vendor Text R
Sensor
Intelligence
RefertoIO-Linkspecication.
19 ProductID 8 x 8Bit R 6038664
RefertoIO-Linkspecication.
This SPDU refers to the corresponding IODD. It corre-
spondstothevirtualordernumberoftheentireproduct
family.
21 Serial Number 8 x 8Bit R
Production ID of the SICK pressure switch. It contains
alphanumeric characters.
24
ApplicationSpecic
Name
16 x 8Bit R/W
Thetextcanbedenedbytheuser.Itservesasidentica-
tion of the pressure switch within a network.
33 LastEvent 8Bit + 16Bit R RefertoIO-Linkspecication.
40 ProcessDataIn 16Bit R
ThisSPDUreectstheprocessdataastheyarealso
cyclicallytransmitted(seeabove).
243 OrderNo R
In contrast to the ProductID this SPDU refers to the actual
order number of the pressure switch.
SICK-specic
Index
(dezimal)
Name Format Access Range Remark
65
SP1/
FH1
16 Bit
unsigned
R/W 1040-9000
Correspondstotheprocessvalueatwhichtheswitchisactivated(closed,
Q+24V)ortotheupperlimitinthewindowmode.Incaseoftheoutput
being parametrized as „Hnc“ or „Fnc“ (normally closed), the logic is
inverted.ThevalueofRP1/FL1shallbeatleast40units(0,5%ofthe
measuringrange)lowerthanthevalueofSP1orFH1,respectively.Ifthis
isnotthecase,RP1orFL1aresettothenearestpossiblevalue.