Operating Instructions PBS
SIO Mode yes
Min. cycle time 2.3 ms
Data rate COM2 (38.4 kBaud)
Process data format 16 bit (frame type 2.2)
Description of IO-Link functionality (if available)
7. Starting, operation
7. Starting, operation
Physical Layer
Process Data
The SICK pressure switch has one or two digital outputs. Both switching outputs are transmitted as
processdataviaIO-Link.TheswitchingoutputQ2isalsoavailableatpin2oftheM12connector.In
theSIOmodetheswitchingoutputC/Q1isavailableatpin4oftheM12connector.
Inthecommunicationmodethispinisexlusivelyusedforcommunication.Informationfromthe
pressureswitcharetransmittedusing"frametype2.2".Bit0containstheswitchingstateofswitch
Q1whereasbit2containstheswitchingstateofswitchQ2.Thedigit1correspondstothelogical
state"closed"orto+24Vonthecorrespondingoutput,respectively.
Theremaining14bitsreecttheanalogmeasurementvalueofthepressureswitch.Theanalog
pressuremeasurementvalueismappedtoarangeof0to10000(digits).Thelowerendofthe
measuringrange(MBA)correspondstothevalue1000whereastheupperendofthemeasuring
range (MBE) corresponds to 9000. Hence, it is required to know the measuring range of the sensor
in order to translate the transmitted continuous measurement signal into the actual pressure.
MSB LSB
Pressurevalue
Q2 Q1