Further information:
Max. Process data In: 277 byte
Max. Process data Out: 272 byte
Min. IO-Link cycle time: 1 ms
Output current power port (pin1): 500 mA (Maximum device current must not be
exceeded)
Device current consumption: no load: 30 V / 150 mA, 24 V / 175 mA, 18V /
240 mA, 10 V / 355 mA.
Max. Device current: 3 A
Output current (Port S1-S4, pin 4): 200 mA
Initialization time after switch on: 60 s (plus ~30 s additional time per installed
IODD)
Max. number of I/Os which can be connected: 52 I/Os (together with 4 SIG100)
Max. number of IO-Link signals which can be
connected:
4
Ethernet Ports: 2
Max. Output frequency: 35 Hz
12
1
With basic logic, not gate logic
2
Max. frequency will vary depending on logic configuration
IO-Link:
Specification: V1.1.
Port Class: A
Transfer rate: COM1 / COM2 / COM3
Input specification: IO-Link specification EN61131-2, type 1
Transfer rate recognition: automatic
Product safety
Table 27: Product safety data
Protection class 3
Short-circuit protection in accordance with VDE 0160
12 TECHNICAL DATA
100
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200 8017853/2019-06-06 | SICK
Subject to change without notice