Technical Data
3ZX1012-0RB22-1AA1 23
English
Short-circuit
protection
Main circuit (current measurement module):
refer to catalog
Control circuit:
Fuse links utilization category gL/gG 6 A
Thermistor
protection
Thermistor sensor in the motor is connected to terminals T1/T2
Summated cold resistance R
cold
≤
1.5 k
Ω
Measuring circuit load
≤
5mW
(at R
cold
= 1.5 k
Ω
)
Sensor circuit voltage
≤
2V
(at R
cold
= 1.5 k
Ω
)
Open circuit voltage < 30 V
Operating value overload 3.4 to 3.8 k
Ω
Release value 1.5 to 1.65 k
Ω
Short-circuit detection 10 to 20
Ω
Ground-fault
protection
The following data refers to sinusoidal fault currents of 50/60 Hz:
With a motor current between the 0.3- and 2-fold set currentI
e
, the
unit trips at an ground-fault current that is 30 % of the set current.
With a motor current between the 2- and 8-fold set currentI
e
, the unit
trips at an ground-fault current that is 15 % of the motor current.
The on-delay is 0.5 to 1 s.
Also refer to
diagram VII
in the graphic section (I
GF
= ground-fault
current, I
trip_GF
= operating current in the event of a ground fault).