Communication System Manual 3WN6 Circuit-Breakers
Version 1.0 (05/98) Copyright Siemens AG 1998. All rights reserved. 39
3.4.2 List of acyclic 3WN6 messages on PROFIBUS-DP
x =
1 Test unit + delivery
date
500, 1, 0, 0, 0 1 - 111194 - -
2 Identifier number 500, 2, 0, 0, 0 0 - 99 - -
4 Rated current of
circuit-breaker
500, 4, 0, 22, 0 315 - 3200 A 315 - 3200 A 315 - 3200 A
5 Function test of
release
500, 5, 0, 0, 0
0 - 3
19
)
0 - 3
19)
0 - 3
19)
11 Circuit-breaker size 502, 1, 0, 0, 0 1 - 2 - -
12 Circuit-breaker
type
502, 2, 0, 0, 0 2 - -
13 No. of poles 502, 3, 0, 0, 0 3 - 4 - -
14 Version of release
unit (in ASCII
code)
502, 4, 0, 0, 0 "N" or "P"
(ASCII code)
"H" or "J"
(ASCII code)
"D" or "E"
(ASCII code)
15 Revision level of
communication
502, 5, 0, 0, 0 (2 bytes:
hardware +
software)
(2 bytes:
hardware +
software)
(2 bytes:
hardware + software)
16 Communication
module version
502, 6, 0, 0, 0
11; 91
20
)
11
20)
11
20)
17 Revision level of
release unit
502, 7, 0, 0, 0 (2 bytes:
hardware +
software)
(2 bytes:
hardware +
software)
(2 bytes:
hardware + software)
21 Communication
address
503, 1, 0, 0, 0
21
) 21) 21)
17)
The message addresses are shown as decimal numbers in the following; input must be in binary format.
18)
The value ranges shown here and on the following pages are transferred in the corresponding binary format.
19)
0: System 0K; 1: Bus error; 2: CT recognition module error; 3: LCD error.
20)
11: Communication functions (Z=F01 in order number); 91: Communication and measurement functions (Z=F05)
21)
Not supported at present.
Message group 0
M.
no.
Designation Message
address
17)
Value range
18)
Value range
18)
Value range
18)
0:x Circuit-breaker
key data
Releases
N and P
Releases
H and J/K
Releases
D and E/F
Note: Circuit-breaker key data, i.e. messages 0:1 to 0:21 are "read only" data.