Communication System Manual 3WN6 Circuit-Breakers
Version 1.0 (05/98) Copyright Siemens AG 1998. All rights reserved. 43
T-
Nr.
RELEASE N and P H and J/K D and E/F
Message address
1:2 "Tripped" signals
29)
742, 1, 0
The input of octet strings OS1 to OS4 is not required for the message address in this case.
OS1:7
Earth fault release
("g" release)
OS1:6
X X X
OS 1:6 for releases E/F, J/K and P only
Delayed short-circuit
release ("z" release)
OS1:5
X X X
Overload release
("a" release)
OS1:4
X X X
OS1:3
OS1:2
OS1:1
OS1:0
OS2:7
OS2:6
OS2:5
OS2:4
OS2:3
OS2:2
OS2:1
OS2:0
OS3:7
OS3:6
OS3:5
OS3:4
OS3:3
OS3:2
OS3:1
OS3:0
OS4:7
OS4:6
OS4:5
OS4:4
OS4:3
OS4:2
Overload release in N
conductor ("N" release)
OS4:1
X X X
Instantaneous short-circuit
release ("n" release)
OS4:0
X X X
29)
If one bit of the "Tripped" signals is set, this activates a group fault signal (in the cyclic output data).