Fail-Safe Modules 
  7.5 4/8 F-DI DC24V PROFIsafe Digital Electronic Module 
ET 200S Distributed I/O System - Fail-Safe Modules 
Installation and Operating Manual, 08/2008, A5E00103686-07 
117 
7.5.7  Application 2: Safety mode SIL3/Category 3/PLe 
Assigning Inputs to Each Other 
The EM 4/8 F-DI DC24V PROFIsafe has 8 fail-safe inputs, DI 0 through DI 7 (SIL2). A pair of 
these inputs can each be used as one input (SIL3). The following assignment applies:  
●  DI 0 with DI 4 
●  DI 1 with DI 5 
●  DI 2 with DI 6 
●  DI 3 with DI 7 
Sensor supply  
The EM 4/8 F-DI DC24V PROFIsafe provides sensor supply Vs1 for Inputs 0 to 3 and sensor 
supply Vs2 for Inputs 4 to 7. The sensors can be powered internally or externally. 
Wiring Diagram for Application 2.1 - Connecting one channel of one sensor to two inputs 
Single-channel connection of a sensor to two inputs of the F-module for each process signal 
(1oo2 evaluation).  
 
 
Note 
If you power the sensors from the F-DI module, you must use the internal sensor supply Vs1. 
Connection to Vs2 is not possible.