Fail-Safe Modules   
7.2 PM-E F pm DC24V PROFIsafe Power Module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
62  Installation and Operating Manual, 08/2008, A5E00103686-07 
7.2  PM-E F pm DC24V PROFIsafe Power Module 
7.2.1  Properties of the PM-E F pm DC24V PROFIsafe Power Module 
Order Number  
6ES7138-4CF03-0AB0 
Properties 
The PM-E F pm DC24V PROFIsafe power module possesses the following properties: 
●  2 relays for switching the voltage buses P1 and P2, output current = 10 A 
●  2 fail-safe digital outputs, P/M-switching, output current 2 A 
●  Rated load voltage 24 VDC 
●  Suitable for solenoid valves, DC contactors and indicator lights 
●  Group fault display (SF; red LED) 
●  Status display for each output (green LED) 
●  Status display for load current power supply (PWR; green LED) 
●  Assignable diagnostics 
●  Achievable safety classes are listed in the table below 
 
 
 
Note 
The PM-E F pm DC24V PROFIsafe power module is not suitable for the supply of F-SMs.
 
Table 7- 1  Overview of available safety classes with PM-E F pm DC24V PROFIsafe 
PM-E F pm DC24V PROFIsafe  Maximum Attainable Safety 
Class 
Signal switches 
daily or more often 
SIL3/Category 4/PLe Without standard DO 
modules 
Signal switches 
less than once a 
day 
SIL2/Category 3/PLd 
Relay outputs P1 
and P2 
With standard DO modules 
refer to the Internet 
(http://support.automation.siemens.com/WW/vi
ew/en/12461959/133300) 
SIL2/Category 3/PLd 
Electronic outputs 
DO 0 and DO 1 
refer to the applications in the "Wiring of the 
PM-E F pm DC24V PROFIsafe (Page 70)" 
chapter. 
SIL3/Category 4/PLe