Fail-Safe Modules 
  7.7 4 F-DO DC24V/2A PROFIsafe digital electronic module 
ET 200S Distributed I/O System - Fail-Safe Modules 
Installation and Operating Manual, 08/2008, A5E00103686-07 
173 
Causes of Faults and Corrective Measures    
The following table contains the possible causes of the faults described for the individual 
diagnostic messages of the EM 4 F-DO DC24V/2A PROFIsafe and remedies. 
Table 7- 37  Diagnostic messages of the EM 4 F-DO DC24V/2A PROFIsafe, causes of errors and 
remedies 
Diagnostic 
Message 
Fault 
Detection 
Possible Causes  Corrective Measures 
Short circuit in the actuator  Eliminate the short-circuit 
Cross circuit in the actuator Eliminate the cross-circuit within 100 
hours after the error has occurred. 
Short circuit  Always 
Internal error  Replace module 
Overload  For "1" 
output signal 
only 
Output stage is overloaded 
and becomes too hot 
Eliminate overload 
Overtemperat
ure 
Always  Shutdown due to violation 
of upper or lower 
temperature limit value in 
the module case 
Check load wiring, check ambient 
temperature, check whether permissible 
output current (total current) is 
exceeded for the ambient temperature. 
Once the fault has been eliminated, the 
module must be removed and inserted 
or the power switched off and on. 
Wire break  For "1" 
output signal 
only 
Line break  Eliminate broken wire, ensure specified 
minimum load (see Technical 
Specifications) 
Internal error  Always  Internal module fault has 
occurred 
Replace module 
Inserted module does not 
match configuration. 
Incorrect parameter 
assignment. 
Correct the configuration (compare 
actual and preset configuration), check 
communication paths  
Correct configuration 
Parameter 
assignment 
error 
Always 
PROFIsafe address set 
incorrectly in the F-module 
Check whether the PROFIsafe address 
on the module matches the 
configuration in 
HW Config
 
Sensor 
voltage or 
load voltage 
missing 
Always  No supply voltage or 
supply voltage is too low 
Check the supply voltage on the 
interconnected PM, check the module 
for correct contact 
Error in communication 
between F-CPU and 
module, e.g. due to 
defective PROFIBUS 
connection or higher than 
permissible EMI 
Test PROFIBUS/PROFINET 
connection. Correct faults 
PROFIsafe monitoring time 
set too low 
Set a greater value for the "F monitoring 
time" parameter for the module in 
HW Config
 
Communicatio
n error 
Always 
Configuration of the F-
module does not match 
safety program 
Generate safety program again; then 
load configuration and safety program 
into F-CPU again 
Safety-related 
shutdown 
Always  Switching frequency 
exceeded 
Reduce the switching frequency