Configuring 
  2.2 Assigning Modules of an ET 200S 
ET 200S Distributed I/O System - Fail-Safe Modules 
Installation and Operating Manual, 08/2008, A5E00103686-07 
23 
Assigning Power Modules to Electronic Modules/Motor Starters 
The table below lists the power modules and electronic modules/motor starters you can 
operate within the same potential group. 
Note that certain combinations limit the maximum safety class which can be attained. 
Table 2- 3  Assigning Power Modules to Electronic Modules/Motor Starters and Safety Class 
Power Modules  For a 
Description, 
See ... 
Electronic Module/Motor Starter  Use and achievable SIL/Category/PL 
PM-E F pm DC24V 
PROFIsafe  
"Power module 
PM-E F pm 
DC24V 
PROFIsafe" 
PM-E F pp DC24V 
PROFIsafe 
"Power module 
PM-E F pp 
DC24V 
PROFIsafe" 
can be used with all standard electronic 
modules 
Safe shutdown of DO 
modules of the ET 200S 
series 
SIL2/Cat
egory 
3/PLd 
Can only be used for: 
•  F-DS1e-x, F-RS1e-x fail-safe motor 
starters (F-MS) 
•  Connection multiplier F-CM 
•  PM-D F X1 power/expansion 
module 
•  Expansion modules Brake Control 
xB1 and xB2 
Safe shutdown of motor 
starters 
SIL3/Cat.
4/PLe 
PM-D F DC24V 
PROFIsafe 
"Power module 
PM-D F 
DC24V 
PROFIsafe" 
Can be used for the F-motor starters 
indicated above: Brake Control xB3 
and xB4 expansion modules 
Safe shutdown of motor 
starters 
SIL2/Cat
egory 
3/PLd 
Power supply to F-DI, F-DO 
and F-RO modules: 
up to 6ES7138-4FA03-0AB0 
up to 6ES7138-4FC01-0AB0 
up to 6ES7138-4FB02-0AB0 
up to 6ES7138-4FR00-0AA0 
SIL2/Cat
egory 
3/PLd 
PM-E DC24V 
Power Module
 
manual 
PM-E 
DC24V (bis 
6ES7138-
4CA01-0AA0)
 
can be used with all standard and fail-
safe electronic modules 
Supply of F-DI modules, F-
DO modules: 
6ES7138-4FA04-0AB0 
6ES7138-4FB03-0AB0 
SIL3/Cat.
4/PLe